Bus Bar basics
For selection a Busbar must consider the following facts:
01. Rated current at 35 deg.cen.
02. Rated operating
voltage
03. Rated insulation
voltage
04. Protection
degree
05. Allowable rated
short-time withstand current (t = 1 s),unit KA
06. Allowable rated
peak current
07. Maximum thermal
stress I2t (t = 1s)
08. Average
resistance at an ambient temperature of 20°C
Bus bar trunking
is sized to operate at an ambient air which does not exceed + 40 °C and its
average over a period of 24 h does not exceed + 35 °C. Above this value, the
busbar trunking must be derated. If
ambient temperature derating coefficient= k1,then for Busbar trunking
installed indoors Temp=35 k1=1, Temp=40, k1=0.93, Temp=50 k1=0.90, Temp=55 k1=0.86.
Calculation of
the total current (It) is equal to the sum of the currents absorbed by all of
the loads. The loads do not all operate at the same time and, as they are not
continuously at full load, a stacking or simultaneity factor Ks has to be taken
into account It = Σ It load * Ks. Stacking
factor Ks depending on the number of loads according to IEC 60439- 1.For number
of load from 10-40 Ks=0.6,again 40 and more number of loads Ks is 0.5. For
industrial purpose consider 20% more capacity for future expansion.
Thumb rule is, for proper selection of Amp capacity with considering more
safety just multiply copper bus bar cross-section by 1.5 and aluminum bus bar
cross section by 0.8 .
BBT Advantages over cable:
1. BBT system savings material with respect to
cable i.e. cables trays, multiple fixings and also labor costs associated with
multiple runs of cable.
2. Reduced installation time since bus bar
trunking requires less fixings per meter than run cable.
3. Multiple tap-off outlets allow flexibility to
accommodate changes in power requirements subsequent to the initial installation.
4. System is easily extendable.
5. Energy efficient.
Bus Bar
Protection
To protect busbar from overload must set a circuit breaker having current
rating same as max capacity or something less of busbar.
Short time Withstand capability of Bus bar Trunking
The asymmetrical
short-circuit current value is obtained by multiplying the symmetrical
short-circuit current value (Isc) by a standardized asymmetrical coefficient
(k).It is the first value of the 1st transient asymmetrical peak of the
short-circuit which is taken into account.
Example:
For a circuit
with a prospective short-circuit current of 50 kA rms, the 1st peak reaches 105
k (50 kA x 2.1). The short-time withstand value (Icw) of the busbar trunking
must be greater than the current flowing through the installation during the
duration of the short-circuit (Isc) .
According to the
WHO (World Health Organisation), exposure to radiated electromagnetic fields
above 0.2 micro Tesla can be dangerous causing a risk of cancer over the long
term. Some countries have standardized the limit: Sweden = 0.2 µT, at a
distance of 1 meter. All electrical conductors generate a magnetic field, the
strength of which is proportional to the distance between them. The Canalis
busbar trunking concept (metal casing and conductors near together) helps to
considerably reduce radiated electromagnetic fields.
Effects of
harmonics on busbar trunking
Harmonic
currents are caused by non-linear loads connected to distribution systems, i.e.
by loads that draw current with a waveform different that that of the voltage
that supplies them. The most common non-linear loads are equipment including
rectifiers, fluorescent lighting and inverters etc.
Harmonic order is the ratio between the harmonic frequency
fn and the fundamental frequency
(generally the power frequency, 50 or 60 Hz) :n = fn / f.
H3 is heavier
among harmonics, the THD is close to the valueof H3.
Fundamental
frequency: ih1 (50 Hz)
No current in the neutral.
The conductors are correctly
sized.
The only effective solution is
Fundamental
frequency: ih1 (50 Hz) and 33% of
H3
Abnormal temperature rise in the
conductors caused
by current at a higher frequency
in the phases (skin
effect) and current in the
neutral caused by summing
of the H3 harmonics.
Now how can assume amount of harmonics. In
Workshops
Mix
of disturbing loads (computers, UPSs, fluorescent lighting) and non disturbing
loads (motors, pumps,heating).Low probability of harmonics THD ≤ 15%.
But in office Numerous
disturbing loads (computers,UPSs, fluorescent lighting).High probability of
harmonics 15 % < THD ≤ 33%.
Aluminium
Vs Copper busbar trunking
When it comes to
performance and resistance many designers consider copper to offer a higher
performance than aluminum for the same rated bar. However, the differences are
marginal as Lee Jones from Schneider Electric explains:
“Installing
aluminum bus bar trunking with an equivalent performance means that it is
typically between 16% and 25% larger in volume than copper bus bar
trunking.
However, it is 40% lighter, offering contractors a trade-off as it’s easier to
handle, more manageable, requires less people to install it, offers a faster
installation and could eliminate the need for special lifting equipment – all
saving time and money for the contractor and the customer. In addition, the use
of aluminum trunking over copper means the building’s electrical support
structures can be lighter.”
The final argument relates to cost. Even going to a higher rated aluminum
trunking over copper, it still offers financial savings. In cost comparisons
between 3,200A copper versus 4,000A aluminum, there is a saving of 23%.
Lee Jones
comments: “There
are many benefits for choosing aluminum bus bar trunking, which means designers
and contractors shouldn’t be put off from using it. On shorter runs the
performance difference between the two materials is marginal and on longer runs
where volt drop may be an issue, then designers can choose a higher rated
aluminum bar.” In addition, no
special tap-offs are required on our range because of the use of silver on the
joints.
No comments:
Post a Comment