Circuit Breaker selection factors as follows:
01.
Voltage
Rating.
02.
Frequency : Circuit breakers up to
600 amps can be applied to frequencies of 50-120 Hz. Higher than 120 Hz
frequencies will end up with the breaker having to derate. During higher
frequency projects, the eddy currents and iron losses causes greater heating
within the thermal trip components thus requiring the breaker to be derated or
specifically calibrated.
03.
Maximum Interrupting Capacity or breaking capacity: The interrupting rating is generally accepted as the highest
amount of fault current the breaker can interrupt without causing system failure to itself.
Determining the maximum amount of fault current supplied by a system can be
calculated at any given time.
04. Continuous Current Rating: This ampere rating is the continuous current of the breaker
will carry in the ambient temperature(40 deg.) where it was calibrated.
05. Operating Environment : High ambient temperature and altitude(>4000 Ft)
caused derated circuit breaker. At
altitude, the thinner air does not conduct heat away from the current carrying
components as well as denser air found in lower altitudes. In addition to
overheating, the thinner air also prevents
the of building a dielectric charge fast enough to withstand the same voltage
levels that occur at normal atmospheric pressure.
The National Electric Code (NEC)
determines that circuit breakers should handle 80% of their rated capacity for
continuous loads (those being on for three or more hours) and 100% for
intermittent loads. For a total current of 15 A, the calculation is as follows:
15 A * 1.25 = 18.75 A. The installer should use a 20 A CB because the
immediately lower CB rating, 15 A, would not be enough for this load.
So,a thumb rule is first of all
calculate total max. wattage value, then divide by system voltage to get
maximum ampere rating. Now just multiply the ampere value by 1.25 to get
circuit breaker rating.