Long-time Ampere Rating and Delay : This adjustable function
simulates the effect of a bimetal conductor in a thermal-magnetic circuit
breaker. It reacts to overload conditions and determines how much current the
circuit breaker will carry continuously. The nominal pickup point where a
circuit breaker trip unit detects an overload is at 1.075 times the selected
ampere rating. After the circuit breaker has picked up, it will not trip until
the delay determined by the long-time delay adjustment has
been achieved.
Short-time Pickup and Delay : The short-time function allows
the circuit breaker to delay before tripping on high level over currents,
resulting in maximum coordination. I²t IN—results in an inverse-time delay
characteristic that most closely parallels time/current characteristics of
fuses. I²t OUT—results in a constant delay characteristic that coordinates best
with thermal-magnetic and electronic trip circuit breakers.
Instantaneous Pickup : The instantaneous pickup function
simulates the magnetic characteristic of a
thermal-magnetic
circuit breaker. This function trips the circuit breaker with no intentional
time delay. In circuit breakers with both short-time and instantaneous pickup,
the instantaneous pickup will override the short-time pickup if the
instantaneous pickup is set at the same or lower setting than the short-time
pickup.